| FFE-2000 |
All Engineering Data Pages FFE 2000 Data Page
|
 |
|
Projected Beam Detector The system Is comprised of a transmitter which projects a modulated infrared light beam to a receiver. The received signal is analyzed by a controller usually located at ground level. If smoke is present in the beam path for more than 8—10 seconds, a fire relay is activated in the controller. The system is designed to be mounted so that the beam will project between 1ft. (0.305 m) and 2ft. (0.61m) below and parallel to the ceiling. Lateral detection may be up to 30ft. (9.144m) either side of the beam, providing a maximum total coverage area of up to 19,800 square feet (60ft. x 330ft. or 18.288m x 100m). The control unit must be located within 330ft. cable run of the receiver unit. |
Standard Features
- Range of 26.25 ft. to 330 ft. (8m to 100m)
- Separate Transmitter and Receiver Units
- Signal Strength indicating LED’s
- Range 33ft. To 330ft. (10m to 100m)
- Easy set up and alignment
- Internal test switch
- Calibrated obscuration test filter included
- 3 selectable alarm thresholds: 25%, 35% or 50%
- Microprocessor controlled
- Alarm latching or auto reset
- Automatic gain control
- 12 VDC or 24 VDC operation
- Separate alarm and trouble contacts
- Ground Level Control Unit
- Alignment by Universal Bracket
|
|
Smoke Detection If smoke is present in the beam’s path, the received signal is reduced by a level determined by the density of the smoke. If the smoke reduces the signal strength to between the obscuration threshold and 93% for more than 8 to 10 seconds, the fire alarm relay is activated. The alarm threshold may be set to 25%, 35% or 50% to suit the installation.
Operation: The infrared signal is sent from the transmitter via an optical system. At 330 ft. (100m) the diameter of this infrared signal is approximately 10 ft. (3.05m). The wide angle beam arrangement simplifies alignment and increases stability. It is important that the projected beam smoke detector is positioned correctly to minimize the detection time. A fire alarm condition occurs when the smoke obscures the infrared beam. The time to detect a fire condition depends on the location of the smoke beam within the premises, the volume of smoke produced, the construction of the roof, and ventilation considerations. |
Specifications:
The projected beam type smoke detector shall be a 4-wire 12/24 VDC device to be used with a Nationally Recognized Testing Laboratory’s Listed separately supplied 4-wire control panel. Unit shall be listed to U.L. 268 and shall consist of a transmitter, receiver and control box. The detector shall operate between a range of 33ft. to 330 ft. (10m to 100m). The temperature range of the beam shall be -4°F to +131°F (-20°C to +55°C). The beam detector shall feature automatic gain control which will compensate for gradual signal deterioration from dirt accumulation on the lenses. The unit shall include a wall mounting bracket. Testing shall be carried out by using a calibration test filter. The Projected beam type smoke detector shall be a Space Age Electronics, Inc. Fireray 2000.
|
Electrical Specifications:
Primary Input Power
10.2 to 30 VDC
Protection:
100ma Fuse in Control unit
Standby Current
8.5mA @ 24VDC
Alarm Current
16.5 mA @ 24 VDC
Relay Contacts
2A at 30 VDC, resistive
Reset Time
5 Seconds maximum
Start Up Time (Automatic)
45 Seconds
Optical Wavelength:
880nm.
Temperature Rating:
-4°F to +131°F (-20°C to +55°C)
Relative Humidity:
0% to 93% RH non-condensing
Operational Range:
33 ft.- 330 ft. (10m - 100m)
RFI Immunity:
10V/m @ KHz-1 GHz
Field wiring size:
14-24 AWG
Sensitivity:
25%, 35%, 50%
Fire Alarm Thresholds:
1.25dB (25%), 1.87dB (35%), 3dB (50%)
Beam tolerance to misalignment at 35%:
Transmitter +/- 1°
Receiver +/- 4°
Weight-Controller:
4.00 lbs (1.8 kg)
Weight-Transmitter/Receiver:
12 oz. (650 gms.)
Dimensions-Controller:
8.5” W x 10.5” H x 3.5” D
(210mm W x 265mm H x 88mm D)
Dimensions-Transmitter/Receiver (including mounting brackets):
4” W x 3.25” H x 3.75” D
(83mm W x 95mm H x 101mm D)
Unit shipping weight 8 lbs.
|
|
Approvals:
 UL UROX.S3417 ULC UROXC.S3417
 CSFM 7260-1508:101
MEA 293-98-E
|
|