The SM-501 Series Duct Smoke Detector provides early
detection of smoke and products of combustion present in air moving
through HVAC ducts in commercial, industrial and residential applications.
The SM-501 is designed to prevent the re-circulation of smoke by the
air handling systems, fans, and blowers. Complete systems may be shut
down in the event of smoke detection. The
SM-501 model will operate on any one of four input voltages (230VAC,
115VAC, 24VAC or 24VDC). The SM-501 allows up to 30 detectors to
be interconnected for many common functions.
The SM-501 is enclosed in a compact housing.
Each unit provides two sets of 10 Amp form “C” alarm
contacts, along with one set of 10 Amp form “C” trouble
contacts for monitoring head removal and supply voltage failure.
The green pilot and red alarm visual indicators
provided on the front of the SM-501 duct unit signal the operating
status of the device. The green pilot LED will be extinguished when
the detector head is removed. A manual test/reset switch is located
next to the visual indicators.
The SM-501 has been specially designed to allow
common detector functions to be linked between up to 30 detectors.
Specifically, 30 units may be wired to use a common test/reset function,
and to alarm when a single unit alarms. Also, up to 15 units with
signaling devices may be interconnected to operate with a single
alarm. The SM-501 is designed and built to meet all local requirements,
as well as the NFPA regulations regarding duct smoke detectors.
Output terminals are provided for remote accessories such as horns,
strobes, remote status indicators and test/reset key switches or
push buttons.
The ionization and photoelectric detector heads
are interchangeable. Air sampling is accomplished via two tubes
which protrude into the duct. An exhaust tube of one standard length
(7.0") is supplied in the installation kit with the duct smoke
unit. Once the duct width had been determined, the air intake sampling
tubes must be ordered. Sampling tubes are supplied in three standard
lengths (2.5ft, 5.0ft and 10.0ft), and are cut to size to fit the
duct. Mounting the duct smoke detector is accomplished be the use
of a template and four sheet metal screws, as provided. Mounting
can be achieved without the removal of the clear cover, which is
secured by four captive screws.
|
Standard Features:
- Operating voltages 230VAC, 115VA, 24VAC, 24VDC
- Interconnect up to 30 units for common functions
- UL, CSFM and MEA Listed
- Compact Size
- 2 Sets of alarm contacts
- 1 set of trouble contacts
- Rugged steel back box with clear cover
- Compatible with the WP-1 weatherproof enclosure
- Easy retro-fit/upgrade of existing RW Series
detectors
- Clear cover fitted with 4 captive screws
- Large terminal connection screws
- Interchangeable “Plug-In” photoelectric
or ionization heads
- Easy Installation without cover removal (Mechanical)
- Dust filtering in detector head
- No additional screens or filters to clean
- Over 15 remote accessories available
|